Super premium efficiency

Lafert IE4 Motors – AMQE Series

Lafert AMQE super premium efficiency IE4 three-phase motors, 0.75 – 200 kW, aluminium frame 80 – 160 and cast iron frame 180 – 315. For continuous-duty pumps, fans and compressors where every efficiency point pays back. Supplied by KJ Export across the Gulf.

Request a quoteWhatsApp +971 50 269 7191
IE4IEC 60034-30-1IP55Class B riseMade in Italy
Lafert three-phase IEC motor
0.75 – 200 kW2, 4 and 6 poles
Frame 80 – 315aluminium to 160, cast iron 180+
up to 96.7%efficiency (200 kW, 4 pole)
Class B risethermal reserve for hot sites

IE4 vs IE3: what you gain

Nominal efficiency at 400 V 50 Hz, 4 pole, Lafert catalogue values.

RatingIE3 – AMPEIE4 – AMQELosses saved
2.2 kW (frame 100)86.7%89.5%≈ 21%
7.5 kW (frame 132)90.4%92.6%≈ 23%
15 kW (frame 160)92.1%93.9%≈ 23%
55 kW (frame 250)94.6%95.7%≈ 20%

Losses saved = reduction of the motor’s own losses (100% − η). On a motor that runs 8,000 hours a year this is real energy and heat. Compare with Lafert IE3 (AMPE) or see the efficiency class guide.

AMQE electrical data – 400 V 50 Hz

2 pole – 3000 rpm (23 models)
TypekWrpmIn @400 V (A)IE4 η 100%Weight (kg)
AMQE 80Z AA 20.7528951.783.5%9.5
AMQE 80Z BA 21.128652.485.2%11.1
AMQE 90S AA 21.529103.186.5%16.4
AMQE 90L BA 22.229154.388.0%18.0
AMQE 100L AA 2329355.889.1%26.5
AMQE 112M AA 2429507.890.0%33.6
AMQE 132S AA 25.5295510.190.9%58.0
AMQE 132S BA 27.5295914.591.7%59.0
AMQE 132M CA 29.2295316.691.8%68.0
AMQE 160M AA 29.2297016.992.2%88.9
AMQE 160M BA 211296520.392.6%88.9
AMQE 160M CA 215296527.893.3%104
AMQE 180M ZG 222296538.094.0%221
AMQE 200L PG 230297051.594.5%260
AMQE 200L RG 237297063.294.8%309
AMQE 225M PG 245297576.095.0%370
AMQE 250M PG 255297592.695.3%520
AMQE 280S G 275298012695.6%570
AMQE 280M G 290298215195.8%630
AMQE 315S G 2110298018496.0%985
AMQE 315M G 2132298022096.2%1050
AMQE 315L RG 2160298026496.3%1160
AMQE 315L G 2200298032996.5%1200
4 pole – 1500 rpm (24 models)
TypekWrpmIn @400 V (A)IE4 η 100%Weight (kg)
AMQE 90S AA 40.7514451.785.7%16.4
AMQE 90L BA 41.114502.586.7%20.0
AMQE 100L AA 41.114732.587.2%21.5
AMQE 100L BA 41.514703.288.2%25.3
AMQE 100L CA 42.214724.689.5%29.0
AMQE 112M BA 4314646.190.4%38.9
AMQE 132S AA 4414778.191.1%49.0
AMQE 132S BA 45.5147610.891.9%62.0
AMQE 132M CA 47.5147214.592.6%71.0
AMQE 160M AA 49.2148217.993.0%105
AMQE 160M BA 411148221.493.3%110
AMQE 160L CA 415148029.093.9%125
AMQE 180M ZG 418.5148033.094.2%181
AMQE 180L ZG 422148039.194.5%209
AMQE 200L RG 430148053.194.9%280
AMQE 225S PG 437148565.295.2%373
AMQE 225M PG 445148580.295.4%390
AMQE 250M PG 455148596.595.7%553
AMQE 280S G 475149012896.0%655
AMQE 280M G 490149015496.1%730
AMQE 315S G 4110149018596.3%980
AMQE 315M G 4132149022296.4%1031
AMQE 315L RG 4160149026996.6%1093
AMQE 315L G 4200149033296.7%1190
6 pole – 1000 rpm (19 models)
TypekWrpmIn @400 V (A)IE4 η 100%Weight (kg)
AMQE 100L AA 60.759702.082.7%23.0
AMQE 100L BA 61.19662.984.5%25.0
AMQE 100L CA 61.59673.685.9%28.0
AMQE 112M AA 62.29685.387.4%36.5
AMQE 132S AA 639757.088.6%46.0
AMQE 132M BA 649769.589.5%48.0
AMQE 160M AA 65.598110.390.5%105
AMQE 160L BA 67.598116.391.3%115
AMQE 180L ZG 61598528.892.9%245
AMQE 200L PG 618.598535.393.4%265
AMQE 200L RG 62298541.893.7%285
AMQE 225M PG 63099055.494.0%335
AMQE 250M PG 63799067.394.5%471
AMQE 280S G 64599080.694.8%530
AMQE 280M G 65599097.195.1%670
AMQE 315S G 67599013595.4%960
AMQE 315M G 69099016095.6%1070
AMQE 315L RG 611099019595.8%1160
AMQE 315L G 613299023196.0%1250

For Gulf sites: heat, 60 Hz and Saudi IE3

  • Saudi Arabia – SASO 2893: IE3 is mandatory for three-phase motors from 0.75 to 375 kW (380 / 400 V, 60 Hz). Choose IE3 or IE4.
  • 60 Hz: three-phase single-speed motors are marked with a 50 Hz and a 60 Hz voltage range. On 60 Hz with proportionally higher voltage, speed rises by 1.2× and output by 1.15×. Windings for 380 / 400 V 60 Hz are available on request.
  • Ambient above 40 °C: with class B temperature rise the rated output falls to about 95% at 45 °C, 90% at 50 °C, 85% at 55 °C and 80% at 60 °C. A winding utilised to class F needs no derating up to 55 °C – tell us your site temperature.
  • Coastal and outdoor sites: special finish K1 for corrosive chemical and marine atmospheres, anti-condensation heaters and drain holes.

How to read a Lafert type designation

Example: AMPE 90L BA 4. Send us the full type from the nameplate and we identify the exact motor.

AMAsynchronous motor, surface cooled with fan
PEEfficiency: PE = IE3, QE = IE4, HE/EE = IE2, blank = IE1, PH = IE3 NEMA
90IEC frame – shaft height in mm
LFrame length (S, M, L, Z)
BAOutput variant + frame material (A = aluminium, G = cast iron)
4Poles: 2 ≈ 3000, 4 ≈ 1500, 6 ≈ 1000 rpm at 50 Hz

Construction and standards

FeatureStandard design
StandardsIEC 60034, IEC 60072 dimensions, CE (LVD, EMC, RoHS)
Degree of protectionIP55 (higher on request)
InsulationClass F, temperature rise class B (80 K)
Ambient / altitudeup to 40 °C, up to 1000 m
Frame materialAluminium alloy 56 – 160 · cast iron 180 – 315
Terminal boxOn top (left or right possible), entries turnable 90° · removable feet on 71 – 160
MountingIM B3, B5, B14, B35, V1 and others (IEC 60034-7)
PaintRAL 9005 black · K1 finish for marine and chemical atmospheres
Approvals on requestUL, CSA, CQC, EAC, UKCA

Bearings by frame size

FramePolesBearings DE / NDEDimensions (mm)
562 – 46201-2Z12 × 32 × 10
632 – 46202-2Z15 × 35 × 11
712 – 86203-2Z17 × 40 × 12
802 – 86204-2Z20 × 47 × 14
902 – 86205-2Z25 × 52 × 15
1002 – 86206-2Z30 × 62 × 16
1122 – 86306-2Z30 × 72 × 19
1322 – 86208-2Z40 × 80 × 18
1602 – 86309-2Z45 × 100 × 25
1802 – 66311 C355 × 120 × 29
2002 – 66312 C360 × 130 × 31
2252 – 66313 C365 × 140 × 33
2502 – 66314 C370 × 150 × 35
2802 / 4 – 66314 C3 / 6317 C380 × 170 × 39 / 85 × 180 × 41
3152 / 4 – 66317 C3 / NU319 – 6319 C385 × 180 × 41 / 95 × 200 × 45

Bearings are lubricated for life up to frame 160; from frame 180 the motors have regreasing nipples. Roller bearings and oversized bearings are available as options.

Options

  • Thermal protection: PTC thermistors, bimetal N/C or N/O, PT100
  • Anti-condensation heaters (110 or 230 V)
  • Encoder (200 – 2048 ppr) and forced ventilation (MFV)
  • Protective cowl for vertical shaft-down mounting
  • Smaller and oversized B5 / B14 flanges, cast iron endshields
  • Oversized and roller bearings, regreasing device
  • Double shaft and special shaft extensions
  • Vibration grade B, special balancing
  • NEMA C-face (frames 71 – 160)
  • Windings for special voltages and 60 Hz

Frequently asked questions

When does an IE4 motor make sense?

For motors that run many hours a year – pumps, fans, compressors, HVAC – the lower losses usually pay back the price difference. For short or intermittent duty IE3 is often enough.

Does the IE4 AMQE have the same dimensions as IE3?

AMQE uses the IEC frame sizes. In some ratings the IE4 motor needs a longer or larger frame than the IE3 motor of the same kW – check the frame in the table above, or send us your current motor type.

Is IE4 mandatory in the Gulf?

Saudi Arabia requires IE3 (SASO 2893). In the EU IE4 is mandatory from 75 to 200 kW (2 – 6 poles). IE4 always meets an IE3 requirement.

Can AMQE motors run on a frequency inverter?

Yes. Frame 90 and up in standard design are suitable for inverter supply within the limits in the catalogue (peak voltage ≤ 1460 V, dU/dt ≤ 13 kV/µs). Insulated bearings are recommended from 75 kW 2 pole.

Need Lafert IE4 motors?

Send us the kW, poles, voltage and mounting – or your current motor type – and we reply with a quotation.

Data from the Lafert catalogue 10-260/24 at rated voltage. Technical data are subject to change by the manufacturer; final values are confirmed with the quotation. Lafert is a trademark of Lafert S.p.A.